Electrical Thermographic
Services
Serious
findings on ST-BY equipment
This Thermal Image show a poor contact on the main connection to a UPS
battery bank. The loss of efficiency from the battery bank during an
emergency may be critical. Overtemp. on images varies from 1 ºC to
10 ºC
Add some poor connections on the battery’s (in a
serial connection) and the problem is growing (and accelerating) when
the battery bank is most needed to be at a full capacity.
Outgoing
Feeders
The thermograms show various faults on vital equipment starter control
centres.
Poor connection covered by sleeve
Poor cable shoe crimping
Max. 98 °C
Passenger Lift Equipment Control
Control
Equipment
Charger Control Equipment
Mud Pump Control
UPS
Drilling Equipment Control
Inspections
through inspections windows.
HV boards.
Low load outgoing feeder
Outgoing feeder with a high load.
This is an old square type window fitted very close
to the connection. Image is taken from a distance, still the connection
in clearly visible.
Fire
& Gas Equipment
Control equipment on a HV Control Unit
Supply to F&G Cabinet
F&G Control Unit’s
Termination rack connection in instrumentation panel
Starter
Cubicles
Poor connection on a capacitor
Connection in an instrumentation panel
Instrumentation